Product Data & Installation Guide
1
. Product Description
T
hermal Ceramics new FireMaster
®
F
astWrap XL is the thinnest
and lightest flexible wrap material available that passes the ASTM
E2336 test standard required by the 2006 IMC and NFPA 96 for
reduced clearance enclosure materials used to
p
rovide 1 or 2 hour fire rating for kitchen exhaust ducts. The
FastWrap XL core blanket is manufactured using Thermal
Ceramics’ patented Superwool
®
fiber, a 2000°F rated, non-com-
bustible, alkaline-earth silicate wool with low biopersistence.
FastWrap XL is the product of extensive research and development
resulting in break-through improvements in fiberization technology
with significant enhancements in thermal properties beneficial to fire
protection applications. FastWrap XL when used in combination
with an approved firestop sealant provides an effective through
penetration firestop in rated floor and wall assemblies. FastWrap
XL is UL Classified and is part of ULs Listing and Follow-Up Service
Program to ensure the consistent quality essential to the critical
nature of this life-safety application.
Product Features
Approval as a 1 or 2 hour shaft alternative in kitchen grease duct
applications
Zero clearance to combustibles at any location
• Thin and Lightweight at 1
1
2 inch thick, 6 pcf density
• Contours easily to complex duct designs
• Butt Joints on inside layer to save labor and material
• Fully foil encapsulated for fast and clean installation
• Completely inorganic and non-combustible
• Contains 2000°F rated fibers for added safety margin
• Contains no low temperature mineral or glass fibers
• Wide variety of through penetration systems
• Resistant to mold growth (ASTM D6329)
• Extensive Listings and detailed installation instructions
Recognized and accepted by inspectors requiring less job-site
engineering judgments
Available in space saving 50 and 100 square foot rolls for optimal
job-site storage
Available in 48 inch widths for less joints and installation labor
2. Applications
Applied in 2 layers to provide 1 or 2 hour fire protection to grease
ducts exhausting Type 1 hoods per IMC 2006, NFPA 96 and 2006
IAPMO UMC
3. Physical Characteristics
4. Performance Specifications
5. Listings/Building Code Reports
*International Code Council -Engineering Service
Thermal Ceramics
FastWrap
®
XL
Commercial Kitchen Grease Duct
Thermal Ceramics
FireMaster FastWrap XL
Typical Insulation Pin Layout
For Duct Spans > 24" Wide To Prevent Blanket Sag
Figure 3
1. Minimum 12 gauge steel insulation pins
Thermal Ceramics
FastWrap XL
Through Penetration System 1 or 2 Hour Grease Duct
Figure 5
1 Duct
2 Two layers FastWrap XL
3 Scrap pieces of FastWrap XL
4 Approved Through Penetration FireStop Sealant
5 Rated floor or wall
Thermal Ceramics
FireMaster FastWrap XL
Access Door Systems Commercial Kitchen Grease Duct
North America - Sales Offices
Canada
T
: +1 (905) 335 3414
F: +1 (905) 335 5145
Mexico
T: +52 (555) 576 6622
F: +52 (555) 576 3060
United States of America
Eastern T: +1.800.338.9284 F: +1.866.785.2764
Western T:+1.866.785.2738 F: +1.866.785.2760
South America - Sales Offices
Argentina
T
: +54 (11) 4373 4439 F: +54 (11) 4372 3331
Brazil
T: +55 (21) 2418 1366 F: +55 (21) 2418 1205
Chile
T: +56 (2) 854 1064 F: +56 (2) 854 1952
Colombia
T: +57 (2) 2282935/2282803/2282799
F: +57 (2) 2282935/2282803/23722085
Guatemala
T: +50 (2) 4733 295/6
F: +50 (2) 4730 601
Venezuela
T: +58 (241) 878 3164
F: +58 (241) 878 6712
F
ire Protection Products
Duct FireMaster
Fire Protection
Product
Unit Size
Units/
Ctn.
Wt./
Ctn.
FastWrap XL Roll 1
1
2 x 24" x 25' 1 37.5 lbs.
FastWrap XL Roll 1
1
2 x 48" x 25' 1 75 lbs.
FastW
rap XL Collar
Roll 1
1
2 x 6" x 25' 4 37.5 lbs.
Color White blanket with silver foil encapsulation
04.08/7 14-236/5.0M
Reference Standard Standard No. Performance
GreaseDuct Enclosure
System
ASTM E2336 Pass
Section 16.1 - Non-
Combustibility
ASTM E136 Pass
Section 16.2-Fire
Resistanance (wall)
ASTM E119 Pass
Section 16.3 -
Durability Test
ASTM C518 Pass
Section 16.4 -
Internal Fire Test
ASTM E2336 Pass
Section 16.5 - Fire
Engulfment (duct)
ASTM E814/E119 Pass
Surface Burning Characteristics
Flame Spread
(foil/blanket)
ASTM E84 5/0
Smoke Developed
(foil/blanket)
ASTM E84 5/0
Thermal Resistance
(R-value)
ASTM C518 (70F) 4.2 per inch
Mold Growth (75%
humidity)
ASTM D6329 Resistant
Mold Growth (95%
humidity)
ASTM D6329 Resistant
Listed Uses Agency Listing
Grease Duct Enclosure System (Zero
Clearance) - AC101 (ASTM E2336)
UL G18
Grease Duct Enclosure System (Zero
Clearance) - ASTM E2336
ICC-ES* ESR 2213
Through Penetration FireStop System
- ASTM E814/UL 1479
UL C-AJ-7119
Figure 4
1.
DuctMate® F2-HT
Access Door or 16
gauge cover plate
5. Spool pieces
2. All thread rods 6. W
ing nuts and washers
3. Installation pins with speed clips
7.
Outer cover plate
labeled “ACCESS
DOOR-DO NOT
OBSTRUCT”
4.
Three layers FastW
rap XL
with mini
-
mum 1” overlaps and all edges sealed
wtih aluminum tape
FireMaster DuctMate
F2-HT Door System
FireMaster Field
Fabricated Door System
Seitenansicht 0
1 2 3 4 5 6

Inhaltsverzeichnis

Seite 1 - FastWrap

Product Data & Installation Guide1. Product DescriptionThermal Ceramics new FireMaster®FastWrap XL is the thinnestand lightest flexible wrap mater

Seite 2 - Thermal Ceramics

6. Storage: FastWrap XL must be stored in a dry warehouse environment onpallets. Pallets should not be stacked. 7. InstallationFastWrap XL shall be i

Seite 3

6. Storage: FastWrap XL must be stored in a dry warehouse environment onpallets. Pallets should not be stacked. 7. InstallationFastWrap XL shall be i

Seite 4

6. Storage: FastWrap XL must be stored in a dry warehouse environment onpallets. Pallets should not be stacked. 7. InstallationFastWrap XL shall be i

Seite 5

Product Data & Installation Guide1. Product DescriptionThermal Ceramics new FireMaster®FastWrap XL is the thinnestand lightest flexible wrap mater

Seite 6

Product Data & Installation Guide1. Product DescriptionThermal Ceramics new FireMaster®FastWrap XL is the thinnestand lightest flexible wrap mater

Kommentare zu diesen Handbüchern

Keine Kommentare